Fire Sprinkler Systems

Home - Fire Sprinkler Systems

FLEXIBLE SPRINKLER HOSE FITTINGS

Technical Specification:

  • • Available product length and type : 700mm to 1800 (28" to 70")
  • • Available square bar length : 700mm to 1500 (28" to 59")
  • • Max. working pressure : 14 Kgf/cm² (175 psi)
  • • Max. ambient temperature 107°C (225°F)
  • • Minimum installation bending radius 75mm (3")
  • • Bending Angles (Flow Direction) Up to 180°
  • • Largest K factor for 1/2 inch outlet 5.6 [gpm/(psi)/2]
  • • Largest K factor for 3 inch outlet 14.0 [gpm/(psi)/2]
  • • Intended use Wet system and dry system

AUTOMATIC SPRINKLER HEADS

Technical Specification : -

  • • Approval : Bureau of Indian Standards
  • • Minimum Operating Pressure : 7 psi (0.5 bar)
  • • Maximum Working Pressure : 175 psi (12 bar)
  • • Factory tested hydrostatically to 30 bar
  • • Thread size : 1/2" BSP
  • • Nominal Bore or Orifice size : 15mm
  • • Nominal K-Factor or Discharge coefficient : 80±4